Description:
Lapp Core identification code: Up to 0.34 mm²: DIN 47100 cores |
From 0.5 mm²: white cores with black numbers, cores of |
screened pair (2 x 1.0) are marked with no. 1 + 2 |
Conductor stranding: Extra-fine wire |
Torsion: Torsion load max. ± 360 °/m |
Minimum bending radius: Flexible use: 10 x outer diameter |
Fixed installation: 4 x outer diameter |
Nominal voltage: IEC: up to 0.34 mm² 250 Vss. |
0.5 - 2.5 mm² U0/U 300/500 V |
UL/CSA: up to 1.5 mm² 600 V, |
from 2.5 mm² 1000 V |
Test voltage: Up to 0.34 mm²: 1500 V |
From 0.5 mm²: 2000 V |
Protective conductor: G = with GN-YE protective conductor |
X = without protective conductor |
Temperature range: Flexing: -40°C to +80°C |
Fixed installation: -50°C to +80°C |